Buzz | Project Solutions Engineer+86 131 8458 2748
Bella | Application Engineer+86 136 9956 4381sales@sunengelec.com
EN
Start an Enquiry
High Voltage Switchgear

KYN28-12 Armored Draw-Out AC Metal-Clad Switchgear

Product Overview

The KYN28A Armored Draw-out AC Metal-clad Switchgear is designed for three-phase 50Hz AC power systems, used for power reception, distribution, circuit control, protection, and monitoring. This product complies with the following standards: ● GB3906 3.6kV~40.5kV AC Metal-clad Switchgear and Controlgear ● GB/T11022 Common Technical Requirements for High-voltage Switchgear and Controlgear ● IEC62271:2000 AC Metal-clad Switchgear and Controlgear for Rated Voltages above 1kV and up to 52kV ● DL/T404 3.6kV~40.5kV AC Metal-clad Switchgear and Controlgear

Share the model, quantity, drawing, destination and project requirement for a focused response.

Product Features

  • Product Shell Structure The product casing is fully assembled with bolts using aluminum-zinc coated steel plates, formed by multi-stage bending via CNC machine tools. This structure ensures high mechanical strength, effectively maintaining product integrity and aesthetics. The cabinet doors are finished with plastic spray coating, offering strong impact resistance and corrosion protection. The shell achieves an IP4X protection rating.
  • Circuit Breaker Configuration The main switch supports VS1-type vacuum circuit breakers, as well as various domestic series (e.g., VD4, VH1, VK, VJD).
  • Insulation & Technical Advantages
  • For any circuit breaker type, the air insulation distance of bare conductors is ≥125mm, and composite insulation ≥60mm.
  • All circuit breakers feature long service life, high parameters, minimal maintenance, and compact design.

Product Details & Applications

KYN28-12 Armored Draw-Out AC Metal-Clad Switchgear product detail and application view 1
KYN28-12 Armored Draw-Out AC Metal-Clad Switchgear product detail and application view 2

Operating Conditions

  • Ambient Temperature: -15°C to +40°C
  • Humidity Conditions:
  • Daily average relative humidity ≤95%, daily average vapor pressure ≤2.2kPa
  • Monthly average relative humidity ≤95%, monthly average vapor pressure ≤1.8kPa
  • Altitude: ≤1000m
  • Seismic Intensity: ≤8 degrees
  • Surrounding Air: Free from significant contamination by corrosive/flammable gases, water vapor, etc.
  • Vibration: Installation site free from frequent severe vibration

Technical Specifications

ItemsUnitData
Rated voltageKV3.6, 7.2, 12
Rated frequencyHz50
Rated current of circuit breakerA630, 1250, 1600, 2000, 2500, 3150, 4000
Rated current of switchgearA630, 1250, 1600, 2000, 2500, 3150, 4000
Rated short-time withstand currentKA16, 20, 25, 31.5, 40, 50
Rated peak withstand current (peak value)KA40, 50, 63, 80, 100, 25
Rated short-circuit breaking currentKA16, 20, 25, 31.5, 40, 50
Rated short-circuit making current (peak value)KA40, 50, 63, 80, 100, 25
Rated insulation level1min power frequency withstand voltagePhase-to-phase & Phase-to-groundKV25, 30, 42
Rated insulation level1min power frequency withstand voltageIsolating breakKV27, 34, 48
Rated insulation levelLightning impulse withstand voltage(peak)Phase-to-phase & Phase-to-groundKV40, 60, 75
Rated insulation levelLightning impulse withstand voltage(peak)Isolating breakKV46, 70, 85
Protection levelEnclosure: IP4X, Compartment room (door open): IP2X

Model Designation

Model designation diagram for the KYN28 series.

Inquiry Now

Send the model, drawing, BOM or project specification. Our team will respond around the actual selection points.