HHWX-12 Series High Voltage Ring Main Box (Outdoor Switching Station)
Product Overview
HHWX-12 Outdoor Switching Station, as a new generation of automated power distribution equipment, it is developed to meet the practical development needs of power system distribution network automation. It integrates full functions including system monitoring, system control, and system communication—fully satisfying all requirements of distribution network automation—making it an ideal modern outdoor switching device. The enclosure is made of 2.0mm stainless steel or polystyrene panels, with a reasonable cabinet structure: each compact functional unit has independent space, separated by partitions to avoid mutual interference. The inner cabinet can be equipped with HXGN-type ring main units (RMUs) and a “five-proof interlocking” mechanism to prevent misoperation and unauthorized operation. The cabinet surface can be polished or painted according to user requirements. The top cover adopts an air-insulated double-layer structure with ventilation openings: air inlets are located at the lower part of the cabinet, and air outlets are installed at the top, hidden under the roof eave to form bottom-up air convection. This design ensures excellent heat insulation and ventilation performance.
Share the model, quantity, drawing, destination and project requirement for a focused response.
Product Features
- Features prefabricated live-touchable silicone rubber cable heads, fully sealed, fully insulated, and maintenance-free to reliably ensure personal safety.
- Compact structure with a small and aesthetic design, stainless steel double-layer case ensures service life of over 20 years.
- Enables regional maintenance without affecting main grid operation, narrowing the power outage scope.
- Can be equipped with one or multiple SF6 load switches, supporting flexible wiring modes with up to 8 outgoing lines.
- Optional lightning arresters, short-circuit fault indicators, current-limiting fuses, etc., to meet various user requirements.
Product Details & Applications



Technical Specifications
| No. | Items | Unit | Data |
|---|---|---|---|
| 1 | Rated voltage | kV | 12 |
| 2 | Rated current | A | 630 |
| 3 | Power frequency withstand voltage (phase-to-phase/to-ground/terminal) | kV/min | 42/48 |
| 4 | Lightning impulse voltage (phase-to-phase/to-ground/terminal) | kV | 75/85 |
| 5 | Rated breaking current | A | 630 |
| 6 | Rated breaking capacitive current | A | 45 |
| 7 | Rated breaking inductive current | A | 16 |
| 8 | Ground leakage current (capacitive) | A | 165 |
| 9 | Rated peak withstand current for 0.3S | kA | 50 |
| 10 | Rated short-time withstand current for 2S | kA | 20 |
| 11 | Rated making current | kA | 50 |
| 12 | Full-load breaking times | Times | >100 |
| 13 | Operation times at 50kA (making) | Times | 5 |
| 14 | Mechanical switching operation times (opening/closing) | Times | 2000 |
Inquiry Now
Send the model, drawing, BOM or project specification. Our team will respond around the actual selection points.