ZW32-12/630-20 12kV Intelligent Pole-Mounted Circuit Breaker
Product Overview
The ZW32-12/630-20 is a pole-mounted vacuum circuit breaker for outdoor 12 kV distribution. Its solid-insulated poles integrate current and voltage sensors and power-taking components. The source specification table lists the ZW32-12/T630-20 and ZW32-12/T630-20G variants.
Share the model, quantity, drawing, destination and project requirement for a focused response.
Product Features
- Technical specifications No. Item Unit ZW32-12/T630-20 ZW32-12/T630-20G 1 Arc extinguishing chamber type – Vacuum Vacuum 2 Insulating medium – Solid insulation Solid insulation 3 Rated voltage kV 12 12 4 Rated frequency Hz 50 50 5 Rated current A 630 630 6 Rated short-time withstand current kA 20 20 7 Rated short-circuit breaking current kA 20 20 8 Rated peak withstand current kA 50 50 9 Rated short-circuit duration s 4 4 10 Rated short-circuit breaking current breaking times Times ≥30 ≥30 11 Rated operating sequence (ratings should not be reduced for rated operating cycles) – O-0.3s-CO-180s-CO O-0.3s-CO-180s-CO 12 Rated lightning impulse withstand voltage Phase-to-phase and phase-to-ground kV 75 75 (1.2/50μs, peak value) Break kV 85 85 13 Rated power frequency short-time withstand voltage (1min) Phase-to-phase and phase-to-ground kV 42 42 Break kV 48 48 14 Partial discharge of the whole machine (including current and voltage sensors and power supply module) Test voltage kV 14.4 14.4 Partial discharge pC ≤20 ≤20 15 Main circuit resistance μΩ ≤80 ≤130 16 Mechanical stability Times ≥10000 ≥10000 17 Actuating mechanism type – Spring Spring 18 Operation mode – Electric operation with manual opening/closing capabilities Electric operation with manual opening/closing capabilities 19 Operating voltage V DC24 DC24 20 Switch closing time ms ≤60 ≤60 21 Switch opening time ms ≤40 ≤40 22 Opening and closing asynchronism ms ≤2 ≤2 23 Current sensor encapsulated in the pole Rated current ratio Phase sequence 600A/1V 600A/1V Zero sequence 20A/0.2V 20A/0.2V Accuracy level Phase sequence Measurement Class 0.5s, Protection Class 5P10 Measurement Class 0.5s, Protection Class 5P10 Zero sequence Class 1, Protection Class 10P10 Class 1, Protection Class 10P10 Temperature range ℃ -40℃~70℃ -40℃~70℃ Implementation method – Low-power electromagnetic type Low-power electromagnetic type 24 Voltage sensor encapsulated in the pole Rated voltage ratio Phase sequence (10kV/√3)/(3.25V/√3) (10kV/√3)/(3.25V/√3) Zero sequence (10kV/√3)/(6.5V/3) (10kV/√3)/(6.5V/3) Accuracy level Phase sequence Class 0.5 Class 0.5 Zero sequence Class 1 Class 1 Temperature range ℃ -40℃~70℃ -40℃~70℃ Implementation method – Capacitive voltage division Capacitive voltage division Sampling method – Dual-side voltage acquisition (both source and load sides) Dual-side voltage acquisition (both source and load sides) 25 Capacitive Power-taking Power Supply Encapsulated in the Pole Power supply method – Built-in capacitive power supply Built-in capacitive power supply Installation method – Integrated capacitive power supply cast into the insulation pole Integrated capacitive power supply cast into the insulation pole Single-phase rated output power W ≥10±10% ≥10±10% 26 Remote and local lockout function – Optional ≥10±10% 27 Recloser enable/disable function – Optional ≥10±10% 28 Manual closing lockout – N/A N/A 29 Switch enclosure protection level – ≤IP67 ≤IP67 30 Switch service life Year 20 20 Note: The above data is subject to change due to technical improvement.
Product Details & Applications

Technical Specifications
| No. | Item | Unit | ZW32-12/T630-20 | ZW32-12/T630-20G | |
|---|---|---|---|---|---|
| 1 | Arc extinguishing chamber type | - | Vacuum | Vacuum | |
| 2 | Insulating medium | - | Solid insulation | Solid insulation | |
| 3 | Rated voltage | kV | 12 | 12 | |
| 4 | Rated frequency | Hz | 50 | 50 | |
| 5 | Rated current | A | 630 | 630 | |
| 6 | Rated short-time withstand current | kA | 20 | 20 | |
| 7 | Rated short-circuit breaking current | kA | 20 | 20 | |
| 8 | Rated peak withstand current | kA | 50 | 50 | |
| 9 | Rated short-circuit duration | s | 4 | 4 | |
| 10 | Rated short-circuit breaking current breaking times | Times | ≥30 | ≥30 | |
| 11 | Rated operating sequence (ratings should not be reduced for rated operating cycles) | - | O-0.3s-CO-180s-CO | O-0.3s-CO-180s-CO | |
| 12 | Rated lightning impulse withstand voltage | Phase-to-phase and phase-to-ground | kV | 75 | 75 |
| 12 | (1.2/50μs, peak value) | Break | kV | 85 | 85 |
| 13 | Rated power frequency short-time withstand voltage (1min) | Phase-to-phase and phase-to-ground | kV | 42 | 42 |
| 13 | Rated power frequency short-time withstand voltage (1min) | Break | kV | 48 | 48 |
| 14 | Partial discharge of the whole machine (including current and voltage sensors and power supply module) | Test voltage | kV | 14.4 | 14.4 |
| 14 | Partial discharge of the whole machine (including current and voltage sensors and power supply module) | Partial discharge | pC | ≤20 | ≤20 |
| 15 | Main circuit resistance | μΩ | ≤80 | ≤130 | |
| 16 | Mechanical stability | Times | ≥10000 | ≥10000 | |
| 17 | Actuating mechanism type | - | Spring | Spring | |
| 18 | Operation mode | - | Electric operation with manual opening/closing capabilities | Electric operation with manual opening/closing capabilities | |
| 19 | Operating voltage | V | DC24 | DC24 | |
| 20 | Switch closing time | ms | ≤60 | ≤60 | |
| 21 | Switch opening time | ms | ≤40 | ≤40 | |
| 22 | Opening and closing asynchronism | ms | ≤2 | ≤2 | |
| 23 | Current sensor encapsulated in the pole | Rated current ratio | Phase sequence | 600A/1V | 600A/1V |
| 23 | Current sensor encapsulated in the pole | Rated current ratio | Zero sequence | 20A/0.2V | 20A/0.2V |
| 23 | Current sensor encapsulated in the pole | Accuracy level | Phase sequence | Measurement Class 0.5s, Protection Class 5P10 | Measurement Class 0.5s, Protection Class 5P10 |
| 23 | Current sensor encapsulated in the pole | Accuracy level | Zero sequence | Class 1, Protection Class 10P10 | Class 1, Protection Class 10P10 |
| 23 | Current sensor encapsulated in the pole | Temperature range | ℃ | -40℃~70℃ | -40℃~70℃ |
| 23 | Current sensor encapsulated in the pole | Implementation method | - | Low-power electromagnetic type | Low-power electromagnetic type |
| 24 | Voltage sensor encapsulated in the pole | Rated voltage ratio | Phase sequence | (10kV/√3)/(3.25V/√3) | (10kV/√3)/(3.25V/√3) |
| 24 | Voltage sensor encapsulated in the pole | Rated voltage ratio | Zero sequence | (10kV/√3)/(6.5V/3) | (10kV/√3)/(6.5V/3) |
| 24 | Voltage sensor encapsulated in the pole | Accuracy level | Phase sequence | Class 0.5 | Class 0.5 |
| 24 | Voltage sensor encapsulated in the pole | Accuracy level | Zero sequence | Class 1 | Class 1 |
| 24 | Voltage sensor encapsulated in the pole | Temperature range | ℃ | -40℃~70℃ | -40℃~70℃ |
| 24 | Voltage sensor encapsulated in the pole | Implementation method | - | Capacitive voltage division | Capacitive voltage division |
| 24 | Voltage sensor encapsulated in the pole | Sampling method | - | Dual-side voltage acquisition (both source and load sides) | Dual-side voltage acquisition (both source and load sides) |
| 25 | Capacitive Power-taking Power Supply Encapsulated in the Pole | Power supply method | - | Built-in capacitive power supply | Built-in capacitive power supply |
| 25 | Capacitive Power-taking Power Supply Encapsulated in the Pole | Installation method | - | Integrated capacitive power supply cast into the insulation pole | Integrated capacitive power supply cast into the insulation pole |
| 25 | Capacitive Power-taking Power Supply Encapsulated in the Pole | Single-phase rated output power | W | ≥10±10% | ≥10±10% |
| 26 | Remote and local lockout function | - | Optional | ≥10±10% | |
| 27 | Recloser enable/disable function | - | Optional | ≥10±10% | |
| 28 | Manual closing lockout | - | N/A | N/A | |
| 29 | Switch enclosure protection level | - | ≤IP67 | ≤IP67 | |
| 30 | Switch service life | Year | 20 | 20 |