HXGN-24 Fixed-Type Metal-Clad Ring Main Switchgear (RMU)
Product Overview
HXGN-24 Fixed-type metal-clad ring main switchgear (RMU), is a 24kV rated voltage, 50Hz rated frequency AC high-voltage switchgear assembly, primarily used in three-phase AC ring networks, terminal distribution grids, and industrial electrical systems for receiving and distributing electrical energy. It is also suitable for integration into prefabricated substations.
Share the model, quantity, drawing, destination and project requirement for a focused response.
Product Features
- Increase main transformer capacity to strengthen substation power supply capability.
- Improve distribution-line transmission capacity while reducing the number of lines.
- Extend the power supply radius of medium-voltage lines.
- Improve power supply quality in medium-voltage grids.
- Reduce power losses in medium-voltage grids.
- Save non-ferrous metals and land resources.
Product Details & Applications



Operating Conditions
- Altitude: ≤1000m
- Ambient temperature: -35°C to +40°C, maximum daily temperature difference 25°C;
- Relative humidity: Daily average ≤95%, monthly average ≤90%;
- Seismic resistance: Seismic intensity grade 8;
- System rated frequency: 50Hz;
- SF6 annual leakage rate: ≤0.1%;
- Enclosure protection class: IP3X; Note: For orders exceeding the above conditions, please consult our company for customization.
Technical Specifications
| No. | Items | Unit | Data | ||
|---|---|---|---|---|---|
| 1 | Rated voltage | kV | 24 | ||
| 2 | Rated frequency | Hz | 50 | ||
| 3 | Rated current | A | 630 | ||
| 4 | Load switch-Fuse combination cabinet | A | ≤100 | ||
| 5 | Rated short-circuit breaking current | kA | 31.5 | ||
| 6 | Rated making current(Peak) | kA | 50 | ||
| 7 | Rated thermal stable current | kA/S | 20/3 | ||
| 8 | Rated dynamic stable current(Peak) | kA | 75 | ||
| 9 | Insulation level | Power frequency withstand voltage | Phase to phase & to ground | kV/min | 65/1 |
| 9 | Insulation level | Power frequency withstand voltage | Fracture | kV/min | 79/1 |
| 9 | Insulation level | Lightning impulse withstand voltage | Phase to phase & to ground | kV | 125 |
| 9 | Insulation level | Lightning impulse withstand voltage | Fracture | kV | 145 |
| 10 | Rated active load breaking current | A | 630 | ||
| 11 | Rated cable charging breaking current | A | 25 | ||
| 12 | Main circuit resistance | μΩ | ≤300 | ||
| 13 | Rated transfer current | A | 870 | ||
| 14 | Mechanical life | Times | Load switch:3000 | ||
| 14 | Mechanical life | Times | Earthing switch:2000 | ||
| 15 | Dimensions(W×D×H) | mm | 600×1195×2000 |