S13 Series 10–11 kV Oil-Immersed Transformer
Product Overview
S(B)13-M Series
Product Overview
The S13 series three-phase oil-immersed transformers are high-efficiency energy-saving power transformers, designed and manufactured with a fully sealed corrugated tank structure. Temperature and volume changes of transformer oil caused by load fluctuations and ambient temperature variations are fully compensated by the corrugated tank, featuring a sleek appearance, compact footprint, and remarkable economic benefits. Compared with GB/T 6451 standards, S13-M transformers achieve an average 45% reduction in no-load losses, 35% reduction in load losses, and 30% decrease in operating costs, making it a sustainable choice for critical infrastructure projects requiring high efficiency and long-term durability.
Share the model, quantity, drawing, destination and project requirement for a focused response.
Model Definition

Features
Range of application
Technical specifications
|
Rated capacity |
Rated voltage |
Vector group |
No-load loss (W) |
Load loss (W) |
No-load current |
Impedance voltage |
||||||||||
|
HV |
Tapping range (%) |
LV |
11# |
13# |
20# |
22# |
11/13# |
20# |
22# |
11# |
13# |
20# |
22# |
|||
|
30 |
6 |
±5 or ±2×2.5 |
0.4 |
Dyn11 or Yyn0 |
100 |
80 |
70 |
65 |
630/600 |
505/480 |
455/430 |
0.3 |
0.3 |
0.24 |
0.23 |
4 |
|
50 |
130 |
100 |
90 |
80 |
910/870 |
730/695 |
655/625 |
0.24 |
0.23 |
0.24 |
0.23 |
|||||
|
80 |
180 |
130 |
115 |
105 |
1310/1250 |
1050/1000 |
945/900 |
0.22 |
0.18 |
0.21 |
0.20 |
|||||
|
100 |
200 |
150 |
135 |
120 |
1580/1500 |
1265/1200 |
1140/1080 |
0.21 |
0.16 |
0.21 |
0.20 |
|||||
|
125 |
240 |
170 |
150 |
135 |
1890/1800 |
1510/1440 |
1360/1295 |
0.2 |
0.15 |
0.19 |
0.18 |
|||||
|
160 |
280 |
200 |
180 |
160 |
2310/2200 |
1850/1760 |
1665/1585 |
0.19 |
0.14 |
0.18 |
0.17 |
|||||
|
200 |
340 |
240 |
215 |
190 |
2730/2600 |
2185/2080 |
1970/1870 |
0.18 |
0.12 |
017 |
0.16 |
|||||
|
250 |
400 |
290 |
260 |
230 |
3200/3050 |
2560/2440 |
2300/2195 |
0.16 |
0.12 |
0.14 |
0.13 |
|||||
|
315 |
480 |
340 |
305 |
270 |
3830/3650 |
3065/2920 |
2760/2630 |
0.16 |
0.11 |
0.13 |
0.12 |
|||||
|
400 |
570 |
410 |
370 |
330 |
4520/4300 |
3615/3440 |
3250/3095 |
0.16 |
0.11 |
0.13 |
0.12 |
|||||
|
500 |
680 |
480 |
430 |
385 |
5410/5150 |
4330/4120 |
3900/3710 |
0.16 |
0.1 |
0.12 |
0.11 |
|||||
|
630 |
810 |
570 |
510 |
460 |
6200 |
4960 |
4460 |
0.15 |
0.09 |
0.12 |
0.11 |
4.5 |
||||
|
800 |
980 |
700 |
630 |
560 |
7500 |
6000 |
5400 |
0.15 |
0.09 |
0.1 |
0.1 |
|||||
|
1000 |
1150 |
830 |
745 |
665 |
10300 |
8240 |
7415 |
0.14 |
0.09 |
0.1 |
0.09 |
|||||
|
1250 |
1360 |
970 |
870 |
780 |
12000 |
9600 |
8640 |
0.13 |
0.08 |
0.1 |
0.09 |
|||||
|
1600 |
1640 |
1170 |
1050 |
940 |
14500 |
11600 |
10440 |
0.12 |
0.07 |
0.09 |
0.08 |
|||||
|
2000 |
1940 |
1360 |
1225 |
1085 |
18300 |
14640 |
13180 |
0.11 |
0.09 |
0.09 |
0.08 |
5.5 |
||||
|
2500 |
2290 |
1600 |
1440 |
1280 |
21200 |
14840 |
13360 |
0.11 |
0.08 |
0.09 |
0.08 |
|||||
|
3150 |
2750 |
2180 |
24100 |
0.11 |
0.08 |
6 |
||||||||||
Additional Product Overview
S13-M Series Three-Phase Oil-Immersed Transformers, Product Overview, The S13-M series of three-phase oil-immersed transformers offer exceptional efficiency and energy savings, expertly designed with a fully sealed corrugated tank structure. This innovative design accommodates changes in temperature and volume of transformer oil due to load fluctuations and environmental temperature variations. The result is not only a visually appealing product with a compact footprint but also significant economic advantages, Compared to GB/T 6451 standards, S13-M transformers deliver impressive performance improvements, featuring an average reduction of 45% in no-load losses and 35% in load losses. These enhancements translate to a 30% decrease in operating costs, reinforcing the S13-M series as a sustainable choice for critical infrastructure projects that demand high efficiency and long-lasting durability
- S13 Series 11Kv SUNENG Electric Power
Additional Product Overview
Leading manufacturer of 11kV oil-immersed power transformers designed for outdoor applications.
Our products adhere to IEC 60076 standards, ensuring quality and reliability.
We offer OEM and ODM services, providing customized solutions to meet your specific needs.
Benefit from our competitive factory pricing and efficient lead times for bulk orders, making us your ideal partner for power transformation solutions
- 11Kv Oil Immersed Power Transformer SUNENG Electric Power
Product Details


Oil-Immersed Transformer Components
Reference component and partner-factory production images. Components, conservator and breather availability depend on the selected design.
Test Control Panel
Steel control panel operating routine-test circuits (ratio, insulation resistance, dielectric) for safe, standard-compliant testing.
Flange Connection
High-strength bolted flange with machined sealing face and oil-resistant gasket — a leak-free oil path for the long run, and easy to open when service is needed.
Finished Porcelain Bushings
Multi-shed porcelain bushings increase creepage distance to cope with outdoor dust and rain.
Transformer Core and Clamp Structure
Painted steel clamps and tie rods hold the laminations tight to cut noise, with single-point core earthing to prevent floating discharge.
Heat Dissipation Panel
Pressed or welded steel fins, phosphated and powder-coated, enlarge the radiating surface and release heat by natural oil convection.
Silica Gel Breather
The silica gel breather is installed at the end of the conservator breathing pipe. The color-indicating silica gel inside appears blue/purple when dry and turns pink once saturated, allowing a quick visual check for replacement. As the oil volume expands and contracts, the breather continuously filters the air entering the conservator and prevents moisture from reaching the transformer oil — a key component for maintaining insulation performance. The oil cup at the bottom allows oil-level observation and dust separation.
Oil-Immersed Transformer Production Line
Reference image from the partner factory. Standardized line covering assembly, drying, oil filling and painting ensures batch consistency and short lead times for export orders.
10 kV Distribution Transformer Testing Area
Reference image from the partner factory. Finished S11/S13/M units are tested one by one before dispatch, verifying electrical and insulation performance with test reports supplied.
Oil-Immersed Transformer Applications
Typical application scenarios. The installations shown are examples; voltage, capacity and mounting arrangement require project-specific confirmation.
Pole-Mounted Transformer: Rural Supply
Where used: Serves scattered rural loads such as village supply and irrigation wells — pole-mounted for minimal land use, fast installation and low cost.
Outdoor Substation: Regional Grid
Where used: Main-transformer bays of 35–110 kV substations, stepping down and distributing power to cities, towns and industrial load centers.
Solar Power Station: Grid Connection
Where used: Steps up PV inverter output to 10/35 kV for grid connection, coping with strong UV, wide temperature swings and day-full / night-light duty.
Industrial Park: Factory Supply
Where used: Supplies industrial parks, plants and mine processing facilities — production lines, large motors and compressors — with dust-resistant, continuous heavy-load capability.
Inquiry Now
Send the model, drawing, BOM or project specification. Our team will respond around the actual selection points.
Open Full Enquiry Page