S11 Series 10 kV Oil-Immersed Transformer
Product Overview
S(B)11-M Series
Product Overview
The S11 series oil-immersed transformers, purpose-built to fulfill the demands of energy efficiency, silent operation, and robust reliability. Tailored for versatile applications, these transformers thrive in urban-rural power networks, industrial parks, and a spectrum of complex power environments where consistent performance is non-negotiable.
Incorporating cutting-edge technologies and premium-grade materials, the S11 offers outstanding electrical performance. Each unit is meticulously engineered to comply with the rigorous standards of modern power grids, integrating strict energy-saving and eco-friendly protocols. From their optimized core designs to advanced insulation systems, these transformers minimize energy dissipation while ensuring stable operation, making them a cornerstone for critical infrastructure projects that prioritize both performance and sustainability.
Share the model, quantity, drawing, destination and project requirement for a focused response.
Model Definition

Features
Range of application
Technical specifications
|
Rated capacity |
Rated voltage |
Vector group |
No-load loss (W) |
Load loss (W) |
No-load current |
Impedance voltage |
||||||||||
|
HV |
Tapping range (%) |
LV |
11# |
13# |
20# |
22# |
11/13# |
20# |
22# |
11# |
13# |
20# |
22# |
|||
|
30 |
6 |
±5 or ±2×2.5 |
0.4 |
Dyn11 or Yyn0 |
100 |
80 |
70 |
65 |
630/600 |
505/480 |
455/430 |
0.3 |
0.3 |
0.24 |
0.23 |
4 |
|
50 |
130 |
100 |
90 |
80 |
910/870 |
730/695 |
655/625 |
0.24 |
0.23 |
0.24 |
0.23 |
|||||
|
80 |
180 |
130 |
115 |
105 |
1310/1250 |
1050/1000 |
945/900 |
0.22 |
0.18 |
0.21 |
0.20 |
|||||
|
100 |
200 |
150 |
135 |
120 |
1580/1500 |
1265/1200 |
1140/1080 |
0.21 |
0.16 |
0.21 |
0.20 |
|||||
|
125 |
240 |
170 |
150 |
135 |
1890/1800 |
1510/1440 |
1360/1295 |
0.2 |
0.15 |
0.19 |
0.18 |
|||||
|
160 |
280 |
200 |
180 |
160 |
2310/2200 |
1850/1760 |
1665/1585 |
0.19 |
0.14 |
0.18 |
0.17 |
|||||
|
200 |
340 |
240 |
215 |
190 |
2730/2600 |
2185/2080 |
1970/1870 |
0.18 |
0.12 |
017 |
0.16 |
|||||
|
250 |
400 |
290 |
260 |
230 |
3200/3050 |
2560/2440 |
2300/2195 |
0.16 |
0.12 |
0.14 |
0.13 |
|||||
|
315 |
480 |
340 |
305 |
270 |
3830/3650 |
3065/2920 |
2760/2630 |
0.16 |
0.11 |
0.13 |
0.12 |
|||||
|
400 |
570 |
410 |
370 |
330 |
4520/4300 |
3615/3440 |
3250/3095 |
0.16 |
0.11 |
0.13 |
0.12 |
|||||
|
500 |
680 |
480 |
430 |
385 |
5410/5150 |
4330/4120 |
3900/3710 |
0.16 |
0.1 |
0.12 |
0.11 |
|||||
|
630 |
810 |
570 |
510 |
460 |
6200 |
4960 |
4460 |
0.15 |
0.09 |
0.12 |
0.11 |
4.5 |
||||
|
800 |
980 |
700 |
630 |
560 |
7500 |
6000 |
5400 |
0.15 |
0.09 |
0.1 |
0.1 |
|||||
|
1000 |
1150 |
830 |
745 |
665 |
10300 |
8240 |
7415 |
0.14 |
0.09 |
0.1 |
0.09 |
|||||
|
1250 |
1360 |
970 |
870 |
780 |
12000 |
9600 |
8640 |
0.13 |
0.08 |
0.1 |
0.09 |
|||||
|
1600 |
1640 |
1170 |
1050 |
940 |
14500 |
11600 |
10440 |
0.12 |
0.07 |
0.09 |
0.08 |
|||||
|
2000 |
1940 |
1360 |
1225 |
1085 |
18300 |
14640 |
13180 |
0.11 |
0.09 |
0.09 |
0.08 |
5.5 |
||||
|
2500 |
2290 |
1600 |
1440 |
1280 |
21200 |
14840 |
13360 |
0.11 |
0.08 |
0.09 |
0.08 |
|||||
|
3150 |
2750 |
2180 |
24100 |
0.11 |
0.08 |
6 |
||||||||||
Oil-Immersed Transformer Components
Reference component and partner-factory production images. Components, conservator and breather availability depend on the selected design.
Test Control Panel
Steel control panel operating routine-test circuits (ratio, insulation resistance, dielectric) for safe, standard-compliant testing.
Flange Connection
High-strength bolted flange with machined sealing face and oil-resistant gasket — a leak-free oil path for the long run, and easy to open when service is needed.
Finished Porcelain Bushings
Multi-shed porcelain bushings increase creepage distance to cope with outdoor dust and rain.
Transformer Core and Clamp Structure
Painted steel clamps and tie rods hold the laminations tight to cut noise, with single-point core earthing to prevent floating discharge.
Heat Dissipation Panel
Pressed or welded steel fins, phosphated and powder-coated, enlarge the radiating surface and release heat by natural oil convection.
Silica Gel Breather
The silica gel breather is installed at the end of the conservator breathing pipe. The color-indicating silica gel inside appears blue/purple when dry and turns pink once saturated, allowing a quick visual check for replacement. As the oil volume expands and contracts, the breather continuously filters the air entering the conservator and prevents moisture from reaching the transformer oil — a key component for maintaining insulation performance. The oil cup at the bottom allows oil-level observation and dust separation.
Oil-Immersed Transformer Production Line
Reference image from the partner factory. Standardized line covering assembly, drying, oil filling and painting ensures batch consistency and short lead times for export orders.
10 kV Distribution Transformer Testing Area
Reference image from the partner factory. Finished S11/S13/M units are tested one by one before dispatch, verifying electrical and insulation performance with test reports supplied.
Oil-Immersed Transformer Applications
Typical application scenarios. The installations shown are examples; voltage, capacity and mounting arrangement require project-specific confirmation.
Pole-Mounted Transformer: Rural Supply
Where used: Serves scattered rural loads such as village supply and irrigation wells — pole-mounted for minimal land use, fast installation and low cost.
Outdoor Substation: Regional Grid
Where used: Main-transformer bays of 35–110 kV substations, stepping down and distributing power to cities, towns and industrial load centers.
Solar Power Station: Grid Connection
Where used: Steps up PV inverter output to 10/35 kV for grid connection, coping with strong UV, wide temperature swings and day-full / night-light duty.
Industrial Park: Factory Supply
Where used: Supplies industrial parks, plants and mine processing facilities — production lines, large motors and compressors — with dust-resistant, continuous heavy-load capability.
Inquiry Now
Send the model, drawing, BOM or project specification. Our team will respond around the actual selection points.
Open Full Enquiry Page