Buzz | Project Solutions Engineer+86 183 7066 5235
Bella | Application Engineer+86 136 9956 4381sales@sunengelec.com
EN
Start an Enquiry

YBH Series Prefabricated Substation (Chinese Box Type)

Product Features

1. Compact Structural Design
Adopting a modular integrated layout, it occupies 40% less floor area than traditional compact substations, ideal for space-constrained scenarios like urban centers and scenic areas.
2. High-Strength Protective Enclosure
Manufactured from premium steel with IP54 protection rating, it is impact-resistant and corrosion-proof, suitable for complex outdoor environments.
3. Easy Maintenance
With zoned layout of internal electrical components and reserved maintenance access, maintenance efficiency is improved by 50%.
4. Flexible Power Supply Solution
The high-voltage side supports multiple configurations such as ring main units/circuit breaker cabinets, adapting to different power demand scales.
5. Efficient Heat Dissipation System
Featuring intelligent temperature-controlled exhaust design, it operates stably in environments ranging from -25℃ to +40℃.

Operating Conditions

● Ambient Temperature: -25°C to +40°C
● Altitude: ≤2000m
● Relative Humidity: Daily average ≤95%, monthly average ≤90%
● Seismic Resistance: Horizontal acceleration 0.4m/s², vertical acceleration 0.15m/s²
● Installation Environment: Free from severe shocks, heavy pollution, chemical corrosion, conductive dust, or explosive hazards.
Note: In case of non-compliance with normal operating conditions, please consult our company for solutions.

Technical Specifications

Items

Unit

HV electrical equipments

Transformer

LV electrical equipments

Rated voltage

kV

6/10/35

6/0.4, 10/0.4

0.4

Rated capacity

kVA

 

50~6300

 
Rated current

A

200、400、630

 

100~3200

Rated short-circuit breaking current

A

Load switch: 400–600A

 

15~63kA

kA

Combined switch: Dependent on the fuse

 
Rated short-time withstand current

kA

16,20(4s)

 

15(1s)

 

30(1s)

Rated peak withstand current

kA

31.5,50

 

30

 

63

1-min power frequency withstand voltage

kV

Phase-to-ground & phase-to-phase: 32/42/95

25/35 (Oil type)

≤03,2

Isolating break: 36/48/118

20/28 (Dry type)

>0.3,2.5

ightning impulse withstand voltage (peak value)

kV

Phase-to-ground & phase-to-phase: 60/75/180

60/75

 

Isolating break: 70/85/185

Enclosure protection level    

IP54

 
Noise level

dB

 

35

 
SUNENG

Product & Project Support

Questions about this topic? Contact Buzz, Project Solutions Engineer, to discuss your product requirements, drawings or technical documents.

Talk to SUNENG

Search SUNENG

Find products, solutions, project references and articles.