SCB11 Series 10kV Three Phase Dry-type Power Transformer
Product Overview
SCB11 Series Dry-Type Transformers, leveraging exceptional low-noise, low partial discharge, and low-loss performance, the SCB11 series stands as a reliable choice for modern power systems. Featuring a vacuum-pressure epoxy resin casting process, it achieves a fully sealed insulation structure for windings, effectively resisting environmental corrosion. The core utilizes high-permeability grain-oriented silicon steel sheets combined with stepped-lap technology to minimize hysteresis losses, while the windings employ high-purity oxygen-free copper conductors, precision-cast under vacuum to ensure stable and reliable electrical performance.
The thin-insulation multi-layer cylindrical winding design significantly enhances short-circuit withstand capability, complemented by an efficient vibration-damping and noise-reduction system for quiet operation.
With professional design, reliable performance, and comprehensive service, the SCB11 series provides robust support for diverse power applications.
Share the model, quantity, drawing, destination and project requirement for a focused response.
Product Features
- Voltage level: 10~35/0.4kV.
- Capacity: 30~3150kVA.
- High-Efficiency Energy-Saving Design
- Complying with national high-level energy efficiency standards, it significantly reduces no-load and load losses, enhancing energy efficiency throughout the lifecycle.
- High-Level Fire Safety
- Adopting epoxy resin vacuum casting insulation technology, it features excellent flame retardancy, eliminates fire hazards, and is suitable for densely populated areas.
- Strong All-Environment Adaptability
- With special protective structure design, it can stably operate for a long time in extreme temperatures, high humidity, and polluted environments.
- Ultra-Quiet Operation
- Innovative noise reduction technology significantly suppresses vibration noise, with operation quietness exceeding industry standards to meet urban silent requirements.
- Compact and Flexible Installation
- With a modular lightweight structure, it has a reduced volume and supports multi-directional installation to adapt to narrow spaces.
- Zero Pollution & Maintenance-Free
- The oil-free design eliminates leakage risks, and the fully enclosed structure is moisture-proof and rust-proof, achieving an ultra-long maintenance-free cycle.



Technical Specifications

| Rated capacity (kVA) | HV (kV) | Tapping range (%) | LV (kV) | Vector group | No-load loss 10#(W) | No-load loss 11#(W) | No-load loss 12#(W) | No-load loss 13#(W) | No-load loss 14#(W) | No-load loss 18#(W) | Load loss 11#120℃(W) | Load loss 12#120℃(W) | Load loss 13,14#120℃(W) | Load loss 18#145℃(W) | No-load current (%) | Impedance voltage (%) |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 100 | 6,6.3,6.6,10,10.5,11 | ±5 Or ±2×2.5 | 0.4 | Dyn11 or Yyn0 | 400 | 360 | 320 | 290 | 270 | 230 | 1570 | 1415 | 1520 | 0.7 | 4 | |
| 125 | 6,6.3,6.6,10,10.5,11 | ±5 Or ±2×2.5 | 0.4 | Dyn11 or Yyn0 | 470 | 420 | 375 | 340 | 320 | 270 | 1850 | 1665 | 1780 | 0.7 | 4 | |
| 160 | 6,6.3,6.6,10,10.5,11 | ±5 Or ±2×2.5 | 0.4 | Dyn11 or Yyn0 | 540 | 480 | 430 | 385 | 365 | 310 | 2130 | 1915 | 2050 | 0.7 | 4 | |
| 200 | 6,6.3,6.6,10,10.5,11 | ±5 Or ±2×2.5 | 0.4 | Dyn11 or Yyn0 | 620 | 550 | 495 | 445 | 420 | 360 | 2530 | 2275 | 2440 | 0.6 | 4 | |
| 250 | 6,6.3,6.6,10,10.5,11 | ±5 Or ±2×2.5 | 0.4 | Dyn11 or Yyn0 | 720 | 640 | 575 | 515 | 490 | 415 | 2760 | 2485 | 2665 | 0.5 | 4 | |
| 315 | 6,6.3,6.6,10,10.5,11 | ±5 Or ±2×2.5 | 0.4 | Dyn11 or Yyn0 | 880 | 790 | 705 | 635 | 600 | 510 | 3470 | 3125 | 3355 | 0.5 | 4 | |
| 400 | 6,6.3,6.6,10,10.5,11 | ±5 Or ±2×2.5 | 0.4 | Dyn11 or Yyn0 | 980 | 880 | 785 | 705 | 665 | 570 | 3990 | 3590 | 3850 | 0.5 | 4 | |
| 500 | 6,6.3,6.6,10,10.5,11 | ±5 Or ±2×2.5 | 0.4 | Dyn11 or Yyn0 | 1160 | 1040 | 930 | 835 | 791 | 670 | 4880 | 4390 | 4705 | 0.4 | 4 | |
| 630 | 6,6.3,6.6,10,10.5,11 | ±5 Or ±2×2.5 | 0.4 | Dyn11 or Yyn0 | 1340 | 1200 | 1070 | 965 | 910 | 775 | 5880 | 5290 | 5660 | 0.4 | 4 | |
| 630 | 6,6.3,6.6,10,10.5,11 | ±5 Or ±2×2.5 | 0.4 | Dyn11 or Yyn0 | 1300 | 1170 | 1040 | 935 | 885 | 750 | 5960 | 5365 | 5760 | 0.35 | 6 | |
| 800 | 6,6.3,6.6,10,10.5,11 | ±5 Or ±2×2.5 | 0.4 | Dyn11 or Yyn0 | 1520 | 1360 | 1215 | 1095 | 1035 | 875 | 6960 | 6265 | 6715 | 0.35 | 6 | |
| 1000 | 6,6.3,6.6,10,10.5,11 | ±5 Or ±2×2.5 | 0.4 | Dyn11 or Yyn0 | 1770 | 1590 | 1415 | 1275 | 1205 | 1020 | 8130 | 7315 | 7885 | 0.3 | 6 | |
| 1250 | 6,6.3,6.6,10,10.5,11 | ±5 Or ±2×2.5 | 0.4 | Dyn11 or Yyn0 | 2090 | 1880 | 1670 | 1505 | 1420 | 1205 | 9690 | 8720 | 9335 | 0.3 | 6 | |
| 1600 | 6,6.3,6.6,10,10.5,11 | ±5 Or ±2×2.5 | 0.4 | Dyn11 or Yyn0 | 2450 | 2200 | 1960 | 1765 | 1665 | 1415 | 11730 | 10555 | 11320 | 0.25 | 6 | |
| 2000 | 6,6.3,6.6,10,10.5,11 | ±5 Or ±2×2.5 | 0.4 | Dyn11 or Yyn0 | 3050 | 2740 | 2440 | 2195 | 2075 | 1760 | 14450 | 13005 | 14005 | 0.2 | 6 | |
| 2500 | 6,6.3,6.6,10,10.5,11 | ±5 Or ±2×2.5 | 0.4 | Dyn11 or Yyn0 | 3600 | 3240 | 2880 | 2590 | 2450 | 2080 | 17170 | 15445 | 16605 | 0.2 | 6 | |
| 1600 | 6,6.3,6.6,10,10.5,11 | ±5 Or ±2×2.5 | 0.4 | Dyn11 or Yyn0 | 2450 | 2200 | 1765 | 12960 | 11660 | 0.2 | 8 | |||||
| 2000 | 6,6.3,6.6,10,10.5,11 | ±5 Or ±2×2.5 | 0.4 | Dyn11 or Yyn0 | 3050 | 2740 | 2195 | 15960 | 14360 | 0.2 | 8 | |||||
| 2500 | 6,6.3,6.6,10,10.5,11 | ±5 Or ±2×2.5 | 0.4 | Dyn11 or Yyn0 | 3600 | 3240 | 2590 | 18890 | 17000 | 0.2 | 8 |
Applications
High rise buildings, densely populated residential areas, important institutions, airports, subways, stations, ports, petrochemicals, metallurgy and mining, nuclear power plants, submarines, light rails, power plants, and places that require fire and explosion prevention.

Inquiry Now
Send the model, drawing, BOM or project specification. Our team will respond around the actual selection points.
Open Full Enquiry Page